United States-MEPS-Electric chillers - 2003
The Federal Energy Management Program (FEMP) set efficiency requirements for air-cooled and water-cooled electric chillers. Product performance must be measured in accordance with AHRI 550/590 test procedures. Free-cooling and combination chiller-heat pump units are excluded.
Air-Cooled, All Compressors
- Capacity: < 150 tons
- Full-Load Optimized Applications (products must meet both levels)
- Full Load Efficiency: 10.500
- Integrated Part-Load Value (IPLV): 13.700
- Part-Load Optimized Applications (products must meet both levels)
- Full Load Efficiency: 9.700
- Integrated Part-Load Value (IPLV): 15.800
- Capacity: = 150 tons
- Full-Load Optimized Applications (products must meet both levels)
- Full Load Efficiency: 10.700
- Integrated Part-Load Value (IPLV): 14.000
- Part-Load Optimized Applications (products must meet both levels)
- Full Load Efficiency: 9.700
- Integrated Part-Load Value (IPLV): 16.100
Water-cooled, Positive Displacement
- Capacity: < 75 tons
- Full-Load Optimized Applications (products must meet both levels)
- Full Load Efficiency: 0.736
- Integrated Part-Load Value (IPLV): 0.600
- Part-Load Optimized Applications (products must meet both levels)
- Full Load Efficiency: 0.780
- Integrated Part-Load Value (IPLV): 0.500
- Capacity: 75 to 149 tons
- Full-Load Optimized Applications (products must meet both levels)
- Full Load Efficiency: 0.715
- Integrated Part-Load Value (IPLV): 0.560
- Part-Load Optimized Applications (products must meet both levels)
- Full Load Efficiency: 0.750
- Integrated Part-Load Value (IPLV): 0.490
- Capacity: 150 to 299 tons
- Full-Load Optimized Applications (products must meet both levels)
- Full Load Efficiency: 0.651
- Integrated Part-Load Value (IPLV): 0.540
- Part-Load Optimized Applications (products must meet both levels)
- Full Load Efficiency: 0.680
- Integrated Part-Load Value (IPLV): 0.440
- Capacity: 300 to 599 tons
- Full-Load Optimized Applications (products must meet both levels)
- Full Load Efficiency: 0.610
- Integrated Part-Load Value (IPLV): 0.520
- Part-Load Optimized Applications (products must meet both levels)
- Full Load Efficiency: 0.625
- Integrated Part-Load Value (IPLV): 0.410
- Capacity: = 600 tons
- Full-Load Optimized Applications (products must meet both levels)
- Full Load Efficiency: 0.560
- Integrated Part-Load Value (IPLV): 0.500
- Part-Load Optimized Applications (products must meet both levels)
- Full Load Efficiency: 0.585
- Integrated Part-Load Value (IPLV): 0.380
Water-cooled, Centrifugal
- Capacity: < 150 tons
- Full-Load Optimized Applications (products must meet both levels)
- Full Load Efficiency: 0.610
- Integrated Part-Load Value (IPLV): 0.550
- Part-Load Optimized Applications (products must meet both levels)
- Full Load Efficiency: 0.695
- Integrated Part-Load Value (IPLV): 0.440
- Capacity: 150 to 299 tons
- Full-Load Optimized Applications (products must meet both levels)
- Full Load Efficiency: 0.610
- Integrated Part-Load Value (IPLV): 0.550
- Part-Load Optimized Applications (products must meet both levels)
- Full Load Efficiency: 0.635
- Integrated Part-Load Value (IPLV): 0.400
- Capacity: 300 to 399 tons
- Full-Load Optimized Applications (products must meet both levels)
- Full Load Efficiency: 0.560
- Integrated Part-Load Value (IPLV): 0.520
- Part-Load Optimized Applications (products must meet both levels)
- Full Load Efficiency: 0.595
- Integrated Part-Load Value (IPLV): 0.390
- Capacity: 400 to 599 tons
- Full-Load Optimized Applications (products must meet both levels)
- Full Load Efficiency: 0.560
- Integrated Part-Load Value (IPLV): 0.500
- Part-Load Optimized Applications (products must meet both levels)
- Full Load Efficiency: 0.585
- Integrated Part-Load Value (IPLV): 0.380
- Capacity: = 600 tons
- Full-Load Optimized Applications (products must meet both levels)
- Full Load Efficiency: 0.560
- Integrated Part-Load Value (IPLV): 0.500
- Part-Load Optimized Applications (products must meet both levels)
- Full Load Efficiency: 0.585
- Integrated Part-Load Value (IPLV): 0.380
Want to know more about this policy ? Learn more