SNI 6390-2011 on Energy Conservation for Air Conditioners in Buildings
This standard provides guidance on air conditioners for any person involved in planning, implementation, monitoring and building management. The standard comprises technical planning, operation and maintenance, energy conservation, testing and energy analysis.
Minimum efficiency of electrically operated air conditioning equipment:
split < 65.000 BTU/h: COP 2.70; KW/TR 1.303
Variable Refrigerant Value: COP 3,70; KW/TR 0.951
Split Duct: COP 2.60; KW/TR 1,353
Air Cooled Chiller < 150 TR (recip): COP 2.80; KW/TR 1.256
Air Cooled Chiller < 150 TR (screw): COP 2.90; KW/TR 1.213
Air Cooled Chiller> 150 TR (recip): COP 2.80; KW/TR 1.256
Air Cooled Chiller > 150 TR (screw): COP 3.00; 1.172
Water Cooled Chiller < 150 TR (recip): COP 4.00; KW/TR 0.879
Water Cooled Chiller < 150 TR (screw): COP 4.70; KW/TR 0.859
Water Cooled Chiller > 150 TR (recip): COP 4.26; KW/TR 0.826
Water Cooled Chiller > 150 TR (screw): COP 4.40; KW/TR 0,799
Water Cooled Chiller > 300 TR (centrifugal). COP 6.05; KW/TR 0.581
This standard was developed starting from SNI 03-6197.