NTG COGUANOR 11007 Energy Efficiency Classification for Window, Split and Package Type Air Conditioners

Last updated: 3 July 2020

This regulation sets the standards for the voluntary Energy Efficiency Classification for Window, Split and Package Type Air Conditioners as follow:

 

Air conditioners with capacity =7038 W ( = 24000 Btu/h):

  • Class A:
    • window type: EER 2,69 (9,2)
    • with ducts: EER 3,67 (12,5)
    • ductless: EER 3,67 (12,5)
  • Class B:
    • window type: EER 2,57 (8,77)
    • with ducts: EER 3,22 (10,98)
    • ductless: EER 2,75 (9,39)
  • Class C:
    • window type: EER 2,34 (7,98)
    • with ducts: EER 2,34 (7,98)
    • ductless: EER 2,34 (7,98)

 

Air conditioners with capacity > 7 038 W a = 10 553 W (> 24 000 Btu/h a = 36 000 Btu/h)

  • Class A:
    • packaged: EER 3,67 (12,5)
    • with ducts: EER 3,67 (12.5)
    • ductless: EER 3,67 (12.5)
  • Class B:
    • window type: EER 2,26 (7,71)
    • packaged: EER 3,22 (11,00)
    • with ducts: EER 3,22 (11.00)
    • ductless: EER 3,22 (11.00)
  • Class C:
    • window type: EER 2,05 (7,00)
    • packaged: EER 2,60 (8,87)
    • with ducts: EER 2,46 (8.39)
    • ductless: EER 2,46 (8.39)

 

Air conditioners with capacity >10 553 W a 17 589 W (>36 000 Btu/h a 60 000 Btu/h)

  • Class A:
    • packaged: EER 3.67 (12.5)
    • with ducts: EER 3.67 (12.5)
    • ductless: EER 3.67 (12.5)
  • Class B:
    • packaged: EER 3.22 (11.00)
    • with ducts: EER 3.22 (11.00)
    • ductless: EER 3.22 (11.00)
  • Class C:
    • packaged: EER 2.60 (8.87)
    • with ducts: EER 2.60 (8.87)
    • ductless: EER 2.60 (8.87)