ISIRI 10636 Fan coils and ducted fan coils - technical specifications and test method for energy consumption and energy labeling instruction
Energy efficiency classes for CFM 200 fan coils (ground, ceiling):
- Class A
- Cooling Capacity: <8.0 W/(1000Btu/h)
- Heating Capacity: <3.8 W/(1000Btu/h)
- Class B
- Cooling Capacity: 8.0=Y<9.5
- Heating Capacity: 3.8=X<4.0
- Class C
- Cooling Capacity: 9.5=Y<11.0
- Heating Capacity: 4.0=X<4.4
- Class D
- Cooling Capacity: 11=Y<12.4
- Heating Capacity: 4.4=X<4.8
- Class E
- Cooling Capacity: 12.4=Y<14.0
- Heating Capacity: 4.8=X<5.7
- Class F
- Cooling Capacity: 14.0=Y<15.5
- Heating Capacity: 5.7=X<5.9
- Class G
- Cooling Capacity: 15.5=Y<17.0
- Heating Capacity: 5.9=X<6.2
Energy efficiency classes for CFM 300 (ground, ceiling) fan coils:
- Class A
- Cooling Capacity: Y<7.0
- Heating Capacity: X<2.4
- Class B
- Cooling Capacity: 7.0=Y<7.5
- Heating Capacity: 2.4=X<2.7
- Class C
- Cooling Capacity: 7.5=Y<8.5
- Heating Capacity: 2.7=X<3.1
- Class D
- Cooling Capacity: 8.5=Y<9.5
- Heating Capacity: 3.1=X<3.5
- Class E
- Cooling Capacity: 9.5=Y<10.5
- Heating Capacity: 3.5=X<3.9
- Class F
- Cooling Capacity: 10.5=Y<11.5
- Heating Capacity: 3.9=X<4.3
- Class G
- Cooling Capacity: 11.5=Y<12.5
- Heating Capacity: 4.3=X<4.7
Want to know more about this policy ? Learn more (Persian)