Regulations on Energy Labelling and Minimum Energy Performance Requirements for Air Conditioners
This regulation specifies the energy labelling requirements and the Minimum Energy Performance Standard (MEPS) requirements for single-package (such as window type) and split-system non-ducted air conditioners using air- and water-cooled condensers and heat pumps employing air-cooled condensers and ducted air-conditioners using air-to-air heat pumps for residential, commercial and industrial sector as applicable in accordance with Bahrain standards.
The MEPS are set as follows:
Starting from July 2016
- Window type AC:
- 18000 > CC:
- EER at T1: 8.5
- EER at T3: 6.12
- 18000 = CC < 24000
- EER at T1: 8.5
- EER at T3: 6.12
- CC = 24000
- EER at T1: 8.5
- EER at T3: 6.12
- Split type and other types:
- EER at T1: 9.5
- EER at T3: 6.84
Starting from July 2017
- Window type AC:
- 18000 > CC:
- EER at T1: 9.8
- EER at T3: 7.06
- 18000 = CC < 24000
- EER at T1: 9.7
- EER at T3: 6.98
- CC = 24000
- EER at T1: 8.5
- EER at T3: 6.12
- Split type and other types:
- EER at T1: 11.5
- EER at T3: 8.28
Moreover, the information contained in the label shall include the Energy Efficiency Ratio, the Coefficient of Performance and the refrigerant type.
Want to know more about this policy ? Learn more (Arabic and English)