GB 19577-2015: Minimum Energy Performance Standards for water chillers
MEPS for electric water chiller with vapor compression cycle. Energy performance, here indicated through Integrated Part Load Value (IPLV) for different capacity ranges are:
air-cooled or evaporating cooled
- CC = 50 kW: COP 2.50, IPLV 2.80;
- CC > 50 kW: COP 2.70, IPLV 2.90; water-cooled:
water-cooled
- CC = 528 kW: COP 4.20, IPLV 5.00;
- 528 kW < CC = 1163 kW: COP4.70, IPLV 5.50;
- CC > 1163 kW: COP 5.20, IPLV 5.90
IPLV = Integrated Part Load Value
CC = Cooling capacity
COP= Coefficient of Performance
Want to know more about this policy ? Learn more (Chinese)